We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
• 1U 8-Outlet eco PDU
• Outlet level metering
ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage. The PE7208 eco PDUs are intelligent PDUs that contain 8 AC outlets and are available in various IEC or NEMA socket configurations. They provide secure, centralized, intelligent, power management of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center's health environment via sensors*.
Function | PE7208A | PE7208B | PE7208G |
Electrical | |||
Nominal Input Voltage | 100 – 120 VAC | 100 – 240 VAC | 100 – 240 VAC |
Maximum Input Current | 20A Max; 16A(UL de-rated) | 20A Max; 16A(UL de-rated) | 16A Max |
Input Frequency | 50-60 Hz | 50-60 Hz | 50-60 Hz |
Input Connection | NEMA 5-20P | NEMA 6-20P | IEC 60320 C20 |
Input Power | 2400 VA(Max); 1920 VA(UL de-rated) | 4160 VA(Max); 3328 VA(UL de-rated) | 3680 VA(Max) |
Outlet Type | Total : 8 x NEMA 5-20R | Total : 7 x IEC320 C13 + 1 x IEC320 C19 | Total : 7 x IEC320 C13 + 1 x IEC320 C19 |
Nominal Output Voltage | 100 – 120 VAC | 100 – 240 VAC | 100 – 240 VAC |
Maximum Output Current (Outlet) | NEMA 5-20R: 20A(Max); 16A(UL de-rated) | C13: 15A(Max); 12A(UL de-rated) C19: 20A(Max); 16A(UL de-rated) | C13: 10A(Max) C19: 16A(Max) |
Maximum Output Current (Bank) | 20A(Max); 16A(UL de-rated) | 20A(Max); 16A(UL de-rated) | 16A(Max) |
Maximum Output Current (Total) | 20A(Max); 16A(UL de-rated) | 20A(Max); 16A(UL de-rated) | 16A(Max) |
Breakers | 1 x 20A Non-Fuse Breaker | 1 x 20A Non-Fuse Breaker | 1 x 16A Non-Fuse Breaker |
Metering | Outlet level Current, Voltage, VA , PF and KWh Monitoring | Outlet level Current, Voltage, VA , PF and KWh Monitoring | Outlet level Current, Voltage, VA , PF and KWh Monitoring |
Outlet Switching | None | None | None |
Environment Sensor Ports | 2 | 2 | 2 |
Metering Accuracy | Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% | Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% | Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Physical Properties | |||
Dimensions (L x W x H) | 43.24 x 22.04 x 4.40 cm (17.02 x 8.68 x 1.73 in.) | 43.24 x 22.04 x 4.40 cm (17.02 x 8.68 x 1.73 in.) | 43.24 x 22.04 x 4.40 cm (17.02 x 8.68 x 1.73 in.) |
Weight | 2.74 kg ( 6.04 lb ) | 2.74 kg ( 6.04 lb ) | 2.74 kg ( 6.04 lb ) |
Power Cord Length | 3 m | 3 m | 3 m |
Environmental | |||
Temperature (Operating / Storage) | 0 – 50°C / -20 – 60°C | 0 – 50°C / -20 – 60°C | 0 – 50°C / -20 – 60°C |
Humidity (Operating & Storage) | 0 – 80% RH, Non-Condensing | 0 – 80% RH, Non-Condensing | 0 – 80% RH, Non-Condensing |
Compliance | |||
EMC Verification | FCC, Others by Request | FCC, Others by Request | CE, Others by Request |
Safety Verification | TUV-CB, cTUVus, Others by Request | TUV-CB, cTUVus, Others by Request | TUV-CB, CE-LVD, Others by Request |